+441225535040

Mon-Fri: 8:00 - 18:00 UK

Email:

MSA IR5500 Open Path Infrared Gas Detector

  • Sensitive to both small (ppm.meter) and large (LEL.meter) gas leaks using dual detection ranges
  • Ideal for use in harsh environments (-55°C)
  • Single detection beam improves accuracy and reduces drift
  • Continuous self-check for fail-to-safe operation
  • Multiple communication outputs (HART, Modbus, AMS support) provide complete status and control capability in the control room
  • Unitized display makes it easy to operate
  • Automatic gain control compensates for dirty optics, rain, and fog
			
Warning: Undefined variable $term_list in /home/users/o/olil/domains/dolcetrade.com/wp-content/themes/olil2/template-parts/post/content-listing-with-gallery.php on line 76
int(17027) NULL

Made in USA. brand MSA Safety, model IR5500

International delivery to Europe, Asia and Africa.
Our warehouses are located in the UK, UAE and Senegal.

price by request

Available

Available

Advantages

Only the best I&C brands

Our company is a global supplier of control and measuring instruments from well-known world brands

Advantages

Discounts for organisations

We sell high-tech equipment at very low prices. We provide really advantageous conditions for partners

Advantages

Fast delivery across the Europe & Asia

We take care of all logistics and customs clearance of I&C solutions from Europe, USA, China and India

Advantages

Professional advice on device selection

Our specialists are ready to advise you on any technical question. We can find an analogue of any device

Descriptions of MSA IR5500

  • The General Monitors IR5500 is an open path IR gas detector that provides continuous monitoring of hydrocarbon gas concentrations.
  • The system consists of an IR source and receiver which continuously monitors for light hydrocarbons in both the 0 to 5000 ppm meter and 0 to 5 LEL meter range.
  • A 0 to 2000 ppm meter and 0 to 1 LEL meter range is also available for monitoring heavy hydrocarbons.
  • The IR5500 provides two 4 to 20 mA analog signals proportional to each of the above ranges, in addition to a digital display and relay contacts.
  • The IR5500 is easily aligned using the digital display and adjustable mounting arms, therefore it does not require any bulky setup equipment (e.g. digital volt meters, handheld alignment aids). The IR5500’s sensitivity can be checked by placing a test gas film in front of the receiver.
  • The IR5500 is calibrated at the factory and needs no further calibration. It also requires little maintenance save for a periodic visual inspection, test gas film check, and cleaning of the windows to assure dependable performance.
  • Sensor data and status information from the IR5500 can be transmitted up to 9,000 feet to any industrial analog to digital (A/D) converter for use in multipoint computerbased monitoring.

 

Technical specifications of MSA IR5500

System Specifications
Sensor type Infrared Absorption
DUAL RANGES

METHANE

PROPANE

0 to 5000 ppm• meter

0 to 5 LEL• meter

0 to 2000 ppm• meter

0 to 1 LEL• meter

Consult factory for other hydrocarbon gases available

PATH LENGtHS 5-30 m, 20-100 m, 80-150 m
RESPONSE TIME T90 ≤ 3 s
REPEATABILITY ≤ ±5%
LINEARITY ≤ ±5% of full scale for each scale

or ±10% of applied gas, whichever is greater

CLASSIFICATION

HAZ LOC

PERFORMANCE

VERIFIED

CSA/FM:

Class I, Div 1 & 2, Groups B, C, & D;

Class II, Div 1 & 2, Groups E, F, & G

Class III; Type 4X

T3C (Tamb=-60°C to +75°C) T4 (Tamb=-50°C to +65°C) ATEX/IECEx:

II 2 G D, Ex d IIB+H2 T4 Gb Ex tb IIIC

T135°C Db, IP66/67

(Tamb=-55°C to +65°C)

CALIBRATION No calibration required. Field background zero adjustment provided
MODES Setup, alignment, test mode
ACCESSORIES Test gas films, mounting arm, mounting base, scope, attenuation plate
WARRANTY Two years
APPROVALS CSA, FM, ATEX, IECEx, DNV-GL, INMETRO, EAC, CE. SIL 3 suitable. HART registered.
Mechanical Specifications
HOUSING 316 stainless steel
SOURCE 5.3″ dia. x 12.4″ length

(135 mm dia. x 315 mm length)

RECEIVER 5.3″ dia. x 12.4″ length

(135 mm dia. x 315 mm length)

WEIGHT Source: 12.20 lb (5.53 kg)

Receiver: 12.34 lb (5.60 kg)

CONDUIT ENTRIES
¾” NPT (standard), M25 (optional)
Environmental Specifications
OPERATING TEMPERATURE RANGE -67°F to +149°F (-55°C to +65°C)
OPERATING

HUMIDITY RANGE

10-95% RH, non-condensing
Electrical Specifications
INPUT POWER 20 to 36 VDC range, 24 VDC nominal

24 VDC @ 12 W (max.) – source

24 VDC @ 10 W (max.) – receiver (w/relays) Consult factory for lower power consumption options for other configurations

DUAL ANALOG SIGNALS

0 MA*

1.5 MA*

2 MA*

4-20 MA**

4-12 MA***

12-20 MA***

21.7 MA

700 ohm load max.

0-5000 ppm• meter            0-5 LEL• meter Startup/Fault                                         Startup/Fault

Test Gas/Setup                    Test Gas/Setup

Beam Block                           Beam Block

0-5000 ppm• m                   0-5 LEL• m

0-5000 ppm• m                   —

—                                            0-5 LEL• m

Over-range                           Over-range

RELAY RATINGS 8 A @ 250 VAC/8 A @ 30 VDC res. max.

Four (4) SPDT – Fault; ppm Warning,

LEL Warning; and Alarm

RS-485 OUTPUT Modbus RTU with block and single data transfer modes
BAUD RATE 2400, 4800, 9600, 19200, or 38400 BPS
HART Fully HART compliant
EMC PROTECTION Complies with EN 61000-6-4 and EN 50270
SAMPLE CABLE DISTANCES For cable resistance of 3 ohms/1,000 ft, maximum distance between IR5500 and power source @ 24 VDC:

14 AWG – 1,330 ft (405 m) – receiver, 14 AWG – 1,040 (317 m) – source.

DIGITAL DISPlAY LED indication of scale displayed; Two digit, seven segment (auto range change)
STANDARD

CONFIGURATION

IR5500-1-1-1-1-2-2-1-1-1-1 Methane, Dual 0-20 mA, HART,

relays, mounting arm, 20-100 m path length

 

User Guide and Instruction manual for MSA Safety IR5500

You can request the necessary certificates, documentation, instructions and user manuals for MSA Safety IR5500 using the special form.

You can buy MSA Safety IR5500 in UK or Europe at a favourable price in «DOLCHETRADE» by leaving a request on the website, by phone +441225535040 or by email . MSA Safety IR5500 price are subject to change depending on exchange rates. We deliver instruments by transport companies in the United Kingdom and Europe.