GEORGIN Tia 1 Programmable converter

Tia1 temperature converters aimed at converting signals from RTD100 sensor to a standard 4 to 20mA current signal. Din rail mounting product. Certified to be installed in hazardous area (See codification).

			
Warning: Undefined variable $term_list in /home/users/o/olil/domains/dolcetrade.com/wp-content/themes/olil2/template-parts/post/content-listing-with-gallery.php on line 76
int(7605) NULL

Made in France. brand GEORGIN, model Tia 1

International delivery to Europe, Asia and Africa.
Our warehouses are located in the UK, UAE and Senegal.

price by request

Available

Available

Advantages

Only the best I&C brands

Our company is a global supplier of control and measuring instruments from well-known world brands

Advantages

Discounts for organisations

We sell high-tech equipment at very low prices. We provide really advantageous conditions for partners

Advantages

Fast delivery across the Europe & Asia

We take care of all logistics and customs clearance of I&C solutions from Europe, USA, China and India

Advantages

Professional advice on device selection

Our specialists are ready to advise you on any technical question. We can find an analogue of any device

Technical specifications of GEORGIN Tia 1

Electrical data

  • Input: RTD100 2 or 3-wires according to EN60751, Max measuring range -220 to 850°C, Minimum span 10°C
  • Output: 4/20 mA
  • Power supply: Standard model 8V … 30 Vdc, ATEX version 8V … 28 Vdc
  • Accuracy: ≤ 0.1% F.S. or ≤ 0.5°C according to the maximal value Load resistance (Vsupply-8) / 0.0215 Ω
  • Shorted or broken line detection:  Configurable 3.5 mA to 21.5 mA, NAMUR NE43 Upscale 21.5 mA, NAMUR NE43 Downscale 3.5 mA
  • Warm-up time: 5 minutes
  • Response time: < 2 s
  • Drift: Voltage supply: 0.01% of the current in the loop for a variation of 0.1% of Vsupply.Temperature: ≤ 10% of accuracy / degree
  • Line resistance effect: 2-wires RTD – 2.5 °C / Ω, compensation is configurable, 3-wires RTD – 2.5° C / Ω between wires
  • EMC Immunity: < 0.1% F.S.

Mechanical data

  • Housing: Polycarbonate, l = 13 mm, h = 110 mm, p = 110 mm
  • Protection: IP 20
  • Weight: approx. 200 g
  • Working T°: -40°C to 85°C (non ATEX version)
  • Storage T°: -40°C to 85°C
  • Relative humidity: 5% to 95% without condensing
  • Connection: Removable screw terminals
  • Max. wire size: from 1×0,2 mm² to 1×2,5 mm²

Certifications

  • EMC: EN 61326 & IEC 61000-6-2
  • For ATEX and IECEx products:
  • Intrinsic Safety: EN 60079-0 & IEC 61241-0, EN 60079-11 & IEC 60079-11, EN 60079-26 & IEC 60079-26
  • Certificate N°: INERIS 13ATEX0015X & INE13.0022X

User Guide and Instruction manual for GEORGIN Tia 1

You can request the necessary certificates, documentation, instructions and user manuals for GEORGIN Tia 1 using the special form.

You can buy GEORGIN Tia 1 in UK or Europe at a favourable price in «DOLCHETRADE» by leaving a request on the website, by phone +441225535040 or by email . GEORGIN Tia 1 price are subject to change depending on exchange rates. We deliver instruments by transport companies in the United Kingdom and Europe.